When meter works with sensors and conductivity of measuring flow is larger than 50μS/cm, under this circumstance, PVVPB 2*0.12*280mm2 model cable (metal shielded signal line covered with PVC) can be used as communication cable for flow signals. The length of signal cable should be less than 100m.
Signal lines have to be connected to sensors that were assembled by producers. The meter can output equivalent level of exciting shielded signal voltage so that interference on flow measurement signals can reduced by means of decreasing the distributed capacitance of communication cable.
Basic function
● Low frequency square wave excitation, excitation frequency: 1/ 10 Power frequency, 1/ 12 Power frequency;
● Exciting Current: 125mA, 250 mA;
● Empty pipe measuring with no additional pole, continuously measuring, alarm by fixed value ;
● Flow velocity measuring range: 0.1 to15m/s, velocity resolution: 0.5mm/s;
● AC high-frequency switching power supply: 85VAC to 250VAC;
● 24V DC switching power supply: 20VDC to 36VDC;
● Network function: MODBUS(Standard), HART(Optional), GPRS(Optional), PROFIBUS(Optional);
● English and Chinese for choosing(Other language is optional);
● Two integrators insides to record flow and heat.
Meter Terminal Wiring
Symbols and Description of Terminals:
TRA1 |
Entry Temperature Input |
TRA2 |
Entry Temperature Input |
TRA3 |
Entry Temperature Input |
TRB1 |
Outlet Temperature Input |
TRB2 |
Outlet Temperature Input |
TRB3 |
Outlet Temperature Input |
SIG + |
Signal 1 |
SGND |
Signal Ground |
SIG- |
Signal 2 |
DRS + |
Exciting Shielding 1 |
DRS- |
Exciting Shielding 2 |
MTDR |
Reserve |
EXT + |
Exciting Current + |
EXT- |
Exciting Current- |
POUT |
Frequency Output + |
PCOM |
Frequency Output Ground |
IOUT |
Current Output + |
ICOM |
Current Output Ground |
TRX- |
Communication Interface |
TRX+ |
Communication Interface |
LN- |
220V (24V) Power Supply Input |
LN+ |
220V (24V) Power Supply Input |